Vacuum Circuit Breaker 12kV

 

1. General Introduction

 

VS1-12 vacuum circuit breaker is widely used in indoor air-insulated switchgears rated 12kV, 50(60)Hz. It conforms to standards of GB1984、IEC 62271-100:2001、GB11022、IEC 60694 and DL/T 403. Under normal service conditions and within its technical data scope, VS1-12 vacuum circuit breaker can satisfy all kinds of operations of electric grids at normal or accidental conditions, including making and breaking short circuit current.

 

The embedded poles (primary main loop) of VS1-12 vacuum circuit breaker are made by APG techniques, embedding its vacuum arc extinguish chamber and upper and lower wire-outgoing ends with epoxy resin for an integration. The embedded poles improve the distribution of electric field around poles, enhance the insulation reliability, reduce adjustment operations of circuit breakers and pollution outside of chamber, and enhance its environmental applicability.

 

VS1-12 vacuum circuit breaker can made to be fixed type or withdrawable type; installed in the front or laterally installed.

 

 

 

2.Normal Service Condition

  • Ambient temperature: -15℃ ~ +40 ℃
  • Altitude: ≤1000m
  • Relative humidity:daily average relative humidity ≤ 95% monthly average relative humidity ≤ 90% Free from fire, explosion, heavy pollution, chemical corrosion and severe vibration.
  • The earthquake intensity ≤ 8 degree  

 

3.Technical Parameters

 

No. Item Unit Parameter
1 Rated voltage kV 12
2 Rated frequency Hz 50(60)

3

Rated short-time power frequency withstand voltage(1 min) kV 42
4 Rated lightning impulse withstand voltage kV 75
5 Rated current A

630

1250

630

1250

1250

1600

2000

1250,1600

2000,2500

3150

6 Rated short-time withstand current kA 20 25 31.5 40
7 Rated peak withstand current kA 50 63 80 100
8 Rated short-circuit breaking current kA 20 25 31.5 40
9 Rated short-circuit making current kA 50 63 80 100
10 Rated operating sequence /

O-0.3s-CO-180s-CO

O-180s-CO-180s-CO(40kA)

11 Short-circuit current breaking times times 274
12 Rated capacitor bank breaking current A 630/400
13 Mechanical lifespan times 10000~30000

 

 

4.Dimensions (withdrawable type)

 

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

202531.5

202531.5

Fixed tulip contact size (mm)

Φ35

Φ49

Pole to pole distance (mm)

150

 

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Fixed tulip contact size (mm)

Φ35

Φ49

Pole to pole distance (mm)

210

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

202531.5

Fixed tulip contact size (mm)

Φ35

Φ49

Pole to pole distance (mm)

275

 

 

 

Rated current (A)

1600

2000

Rated short-circuit breaking current (kA)

31.5,40

31.5,40

Fixed tulip contact size (mm)

Φ55

Φ79

Pole to pole distance (mm)

210

 

Rated current (A)

1600

2000

Rated short-circuit breaking current (kA)

31.5,40

31.5,40

Fixed tulip contact size (mm)

Φ55

Φ79

Pole to pole distance (mm)

275

 

Rated current (A)

2500

3150

4000

Rated short-circuit breaking current (kA)

31.5,40

31.5,40

31.5,40

Fixed tulip contact size (mm)

Φ109

Pole to pole distance (mm)

275

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Fixed tulip contact size (mm)

Φ35

Pole to pole distance (mm)

150

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Fixed tulip contact size (mm)

Φ35

Pole to pole distance (mm)

210

 

 

Dimensions (fixed type)

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

150

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

210

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

275

 

Rated current (A)

1600

2000

Rated short-circuit breaking current (kA)

31.5,40

31.5,40

Pole to pole distance (mm)

275

 

Rated current (A)

2500

3150

4000

Rated short-circuit breaking current (kA)

31.5,40

31.5,40

31.5,40

Pole to pole distance (mm)

275

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

150

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

210