Vacuum Circuit Breaker 24kV

 

1. General Introduction

 

VS1-24 vacuum circuit breaker is widely used in indoor air-insulated switchgears rated 24kV, 50(60)Hz. It conforms to standards of GB1984、IEC 62271-100:2001、GB11022、IEC 60694 and DL/T 403. Under normal service conditions and within its technical data scope, VS1-24 vacuum circuit breaker can satisfy all kinds of operations of electric grids at normal or accidental conditions, including making and breaking short circuit current.

 

The embedded poles (primary main loop) of VS1-24 vacuum circuit breaker are made by APG techniques, embedding its vacuum arc extinguish chamber and upper and lower wire-outgoing ends with epoxy resin for an integration. The embedded poles improve the distribution of electric field around poles, enhance the insulation reliability, reduce adjustment operations of circuit breakers and pollution outside of chamber, and enhance its environmental applicability.

 

VS1-24 vacuum circuit breaker can made to be fixed type or withdrawable type; installed in the front or laterally installed. The structure is similar to 12kV vacuum circuit breakers, but with larger sizes.

 

 

 

2.Normal Service Condition

  • Ambient temperature: -15℃ ~ +40 ℃
  • Altitude: ≤1000m
  • Relative humidity:daily average relative humidity ≤ 95% monthly average relative humidity ≤ 90% Free from fire, explosion, heavy pollution, chemical corrosion and severe vibration.
  • The earthquake intensity ≤ 8 degree  

 

3.Technical Parameters

 

No.

Item

Unit

Parameter

1

Rated Voltage

kV

24

2

Rated Insulation Level

Rated Short-time Power Frequency Withstand Voltage (1 min)

60

Rated Lightning Impulse Withstand

Voltage

125

3

Rated Frequency

Hz

50/60

4

 

Rated Current

A

630

1250

1600

2000

2500

3150

630

1250

1600

2000

2500

3150

630

1250

1600

2000

2500

3150

5

Rated Short Circuit Breaking Current

kA

20

25

31.5

6

Rated Short Time Withstand Current

20

25

31.5

7

Rated Peak Withstand Current

50

63

80

8

Rated Short Circuit Making Current

(Peak Value)

50

63

80

9

Power Frequency Withstand Voltage of

Secondary Loop

V

2000

10

Rated Short Circuit Duration

s

4

11

Mechanical Endurance

times

20000

12

Operation of Breaking Short Circuit Current

times

30

13

Rated Breaking Current of Single Capacitor Tank

A

630

14

Rated Breaking Current of Back-to-back Capacitor Bank

400

15

Rated Operating

Voltage

Closing Coil

V

AC110/220   DC110/220

Opening Coil

AC110/220   DC110/220

Motor for Charging

AC110/220   DC110/220

16

Allowed Worn Thickness of Moving and Fixed Contacts

mm

3

17

Time for Charging

s

≤15

18

Gap Between Open Contacts

mm

13±1

19

Stroke of Contacts

3.5±0.5

20

Opening Time

ms

20~50

21

Closing Time

35~70

22

Average Opening Speed

m/s

1.6±0.2

23

Average Closing Speed

0.8±0.2

24

Rated Operating Sequence

O-0.3s-CO-180s-CO

 

 

4. Dimensions (withdrawable type)

 

 

 

Dimensions (fixed type)

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

210

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

275

 

Rated current (A)

1600

2000

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

275

 

Rated current (A)

2500

3150

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

275

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

210

 

 

Rated current (A)

630

1250

Rated short-circuit breaking current (kA)

20,25,31.5

20,25,31.5

Pole to pole distance (mm)

275

 

Rated current (A)

1600

2000

2500

3150

Rated short-circuit breaking current (kA)

20,25,31.5

Pole to pole distance (mm)

275